Choosing Between VSDs and EC Fans. Making the right investment when upgrading fan technology.

by Emerson Network Power on 7/15/15 3:23 PM

Blog_VSD

Fans that move air and pressurize the data center’s raised floor are significant components of cooling system energy use. After mechanical cooling, fans are the next largest energy consumer on computer room air condition (CRAC) units. One way many data center managers reduce energy usage and control their costs is by investing in variable speed fan technology. Such improvements can save fan energy consumption by as much as 76 percent.

With the different options on the market, it may not be clear which technology is best. Today, variable speed drives (VSDs)—also referred to as variable frequency drives or VFDs—and electrically commutated (EC) fansare two of the most effective fan improvement technologies available. The advantages of both options are outlined below to help data center managers determine which fan technology is best for achieving energy efficiency goals.

How do different fan technologies work? 
In general, variable speed fan technologies save energy by enabling cooling systems to adjust fan speed to meet the changing demand, which allows them to operate more efficiently. While cooling units are typically sized for peak demand, peak demand conditions are rare in most applications. VSDs and EC fans more effectively match airflow output with load requirements, adjusting speeds based on changing needs. This prevents overcooling and generates significant energy savings.

With VSDs, drives are added to the fixed speed motors that propel the centrifugal fans traditionally used in precision cooling units. The drives enable fan speed to be adjusted based on operating conditions, reducing fan speed and power draw as load decreases. Energy consumption changes dramatically as fan speed is decreased or increased due to the fan laws. For this reason, a 20 percent reduction in fan speed provides nearly 50 percent savings in fan power consumption.

EC fans are direct drive fans that are integrated into the cooling unit by replacing the centrifugal fans and motor assemblies. They are inherently more efficient than traditional centrifugal fans because of their unique design, which uses a brushless EC motor in a backward curved motorized impeller. EC fans achieve speed control by varying the DC voltage delivered to the fan. Independent testing of EC fan energy consumption versus VSDs found that EC fans mounted inside the cooling unit created an 18 percent savings. With new units, EC fans can be located under the floor, further increasing the savings.

How do VSDs and EC fans compare?

Energy Savings
One of the main differences between VSDs and EC fans is that VSDs save energy when the fan speed can be operated below full speed. VSDs do not reduce energy consumption when the airflow demands require the fans to operate at or near peak load. Conversely, EC fans typically require less energy even when the same quantity of air is flowing. This allows them to still save energy when the cooling unit is at full load. EC fans also distribute air more evenly under the floor, resulting in more balanced air distribution. Another benefit of direct-drive EC fans is the elimination of belt losses seen with centrifugal blowers. Ultimately, EC fans are the more efficient fan technology.

Cooling Unit Type
VSDs are particularly well-suited for larger systems with ducted upflow cooling units that require higher static pressures, while EC fans are better suited for downflow units.

Maintenance 
In terms of maintenance, EC fans offer an advantage. EC fans also reduce maintenance because they have no fan belts that wear and their integrated motors virtually eliminate fan dust.

Installation 
Both VSDs and EC fans can be installed on existing cooling units or specified in new units. When installing on existing units, factory-grade installation is a must.

Payback
In many cases, the choice between VSDs and EC fans comes down to payback. If rapid payback is a priority, then VSDs are likely the better choice. These devices can offer payback in fewer than 10 months when operated at 75 percent.

However, EC fans will deliver greater, long-term energy savings and a better return on investment (ROI). While EC fans can cost up to 50 percent more than VSDs, they generate greater energy savings and reduce overall maintenance costs, ultimately resulting in the lowest total cost of ownership.

Have the experts weigh in. 
Service professionals can be an asset in helping choose the best fan technology for a data center. Service professionals can calculate the ROI from both options, and they can recommend the best fan technologies for specific equipment.

Service professionals trained in optimizing precision cooling system performance can also ensure factory-grade installations, complete set point adjustment to meet room requirements, and properly maintain equipment, helping businesses achieve maximum cooling unit efficiency today and in the future.

Whether you ultimately decide to go with VSDs or EC fans, either way, you’ll be rewarded with a greener data center, more efficient cooling, and significant energy savings that translate into a better bottom line.


Original Emerson Network Power Blog Post

Read More

Topics: data center energy, PUE, Battery, Efficiency, Thermal Management, DCIM, Uptime, the green grid, AHRI, availability, education, KVM, Data Center efficiency, preventative maintenance

DVL Shines The Spotlight On Data Center For Using “Less Watts"

by Mike Rinaldi on 5/31/13 8:55 AM

-- Award recognizes Conde Nast / CBRE for significantly reducing energy consumption. -- 

cbre conde nast

Bristol, PA – May 29, 2013 –DVL Group, a provider of data center infrastructure management solutions, partnered with 12 data centers to help them save at least 1,000,000 watts of electrical energy.

DVL has officially announced a fourth organization that saved the most watts, which earns them the prestigious Less Watts Award.

The winner of the large category, encompassing data centers greater than 5,000 sq. ft., is Conde Nast / CBRE.  CONGRATULATIONS!!

In addition to honoring the winner with the Less Watts Award, DVL is also making a donation of $1,000 in Conde Nast / CBRE's name to the Delaware Valley Green Building Council (DVGBC).

“The Less Watts competition has been a blast,” says DVL Chief Executive Officer Mike Beck.  “Everyone who participated was incredibly cooperative, enthusiastic and just really great to work with. We couldn’t be happier to present the award to this outstanding organization and look forward to helping others save energy with our “Less Watts” program.”  

To learn more about how DVL helps its customers use Less Watts with quality solutions from industry leader Liebert to build dynamic, energy efficient data centers, visit www.dvlnet.com.

 

Read More

Topics: data center infrastructure, Data Center, Green IT, data center design, data center energy, data center infrastructure management, PUE, efficient data center, DVL, Green Technology, energy, Energy Star, 7x24 exchange

Data Center Infrastructure Management Market to Reach $3.14 Billion

by Mike Rinaldi on 5/7/13 8:16 AM

Data Center Infrastructure Management Market to Reach $3.14 Billion in 2017

The report “Data Center Infrastructure Management (DCIM) Market – by Types (Software, Services & Size of Datacenters); by Industry Verticals (Banking & Finance, Retail, Telecommunications, Healthcare); by Geographies (North America, Latin America, Europe, Asia-Pacific, Middle East & Africa): Global Trends, Technology Advancements, Key Performance Indicators (KPIs), Enterprise Adoption, Competitive Ecosystem, Key Industry Player Profiles, Venture Capital Funding Trends and Worldwide Market Forecasts (2012 – 2017)” defines and segments the global Data Center Infrastructure Management (DCIM) market with analysis and forecasting of the global revenues. It also identifies drivers and restraints for this market with insights on trends, opportunities, and challenges

Read more: http://www.digitaljournal.com/pr/1211474#ixzz2SblA5ssm

dcim

Read More

Topics: data center infrastructure, Data Center, data center design, data center energy, data center infrastructure management, PUE, Green Technology

Is Data Center Infrastructure Management a set of products, a process or both?

by Mike Rinaldi on 5/3/13 1:31 PM

Is DCIM the monitoring, collection and analysis of real-time, continuous, accurate information from an intelligent infrastructure that allows for immediate action, designed to keep the data center in an optimal state of balance between availability, efficiency and capacity?   Is it a framework for operating the data center?

What are your thoughts?

Data center planner

Read More

Topics: Emerson Network Power, data center infrastructure, Data Center, data center design, kW per rack, data center energy, data center infrastructure management, PUE, DVL, electrical distribution, reduce downtime

Do You Prefer Hot Aisle or Cold Aisle Containment?

by Mike Rinaldi on 4/22/13 1:41 PM

Separating the hot and cold air in a data center is one of the keys to improving energy efficiency.  Containment systems don't have to be fancy or expensive.  Containment systems have been in use at least since 2004, but there's an ongoing debate about whether it is best to contain the hot aisle or cold aisle.  

Do you use containment in your data center?  If so, do you contain the hot aisle or cold aisle?"

 cfd

Read More

Topics: data center infrastructure, Data Center, data center design, kW per rack, data center energy, data center infrastructure management, PUE, Containment, efficient data center, DVL, reduce downtime, enclosure, CIO